{"id":63,"date":"2021-05-03T18:04:39","date_gmt":"2021-05-03T12:34:39","guid":{"rendered":"https:\/\/pact.in\/blog\/?p=63"},"modified":"2024-05-21T14:25:56","modified_gmt":"2024-05-21T08:55:56","slug":"sampling-procedures-for-transformer-oil","status":"publish","type":"post","link":"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/","title":{"rendered":"Sampling of Transformer Oil"},"content":{"rendered":"\n<p>In this article, you will learn about preparing of \u2018Electrodes and Test Vessel\u2019 before performing breakdown voltage (BDV) test on insulating oil in service in transformers and switchgear. Below are the steps as defined in IS 6792 that needs to be followed.<\/p>\n\n\n<ol style=\"padding-left: 30px;\">\n<li>Between tests, the oil shall be poured away and the cell left in an inverted position to exclude dirt and moisture, alternatively, the cell shall be filled with oil having high electric strength, and suitably covered.<\/li>\n<li>If the cell has not been used for some time, it should be thoroughly cleaned; the electrodes shall be removed, cleaned and finally rinsed with dry, clean new oil. Replacement of the electrodes should be carried out with the greatest care, avoiding all direct contact with the fingers.<\/li>\n<li>Immediately before use, the cell shall be cleaned by rinsing with the test oil (at least twice) before proceeding to the final filling.<\/li>\n<li>The sampling vessel containing the test oil shall be gently agitated and turned over several times in such a way as to ensure as far as possible a homogeneous distribution of the impurities contained in the oil without causing the formation of air bubbles.<\/li>\n<li>Immediately after this, the sample should be poured down into the test cell, slowly in order to avoid air bubbles forming. The operation is carried out in a dry place free from dust.<\/li>\n<li>The oil temperature at the time of the test shall be the same as that of the ambient air, preferably in the neighborhood of 27\u00baC (15 to 35\u00baC) and noted.<\/li>\n<\/ol>\n\n\n<h2 class=\"wp-block-heading\">Dielectric breakdown voltage test<\/h2>\n\n\n\n<p>This is one of the significant tests to determine the withstanding capacity of insulating oil. It is necessary to test the insulating oils periodically as it degrades due to ingress of moisture.<\/p>\n\n\n\n<p>BDV test is one of the most regular tests done on all insulating fluids, but a very critical one. <\/p>\n","protected":false},"excerpt":{"rendered":"<p>Preparing of \u2018Electrodes and Test Vessel\u2019 before performing breakdown voltage (BDV) test on insulating oil in service in transformers and switchgear, as defined in IS 6792.<\/p>\n","protected":false},"author":1,"featured_media":73,"comment_status":"open","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[10],"tags":[61,62,54,63,57,50,48,55,59,51,52,53,14,15,46,47,11,58,56,60,13,49],"class_list":["post-63","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-oil-test-set","tag-bdv-in-transformer","tag-bdv-machine","tag-bdv-of-oil","tag-bdv-of-transformer-oil-value","tag-bdv-test-in-transformer","tag-bdv-test-of-oil","tag-bdv-test-of-transformer","tag-bdv-tester","tag-bdv-testing-machine","tag-breakdown-voltage-test-of-transformer-oil","tag-dielectric-test-of-transformer","tag-dielectric-test-of-transformer-oil","tag-insulation-oil-tester","tag-oil-bdv-test-kit","tag-oil-bdv-test-of-transformer","tag-oil-dielectric-test-set","tag-oil-test-set","tag-transformer-oil-bdv-test-kit-price","tag-transformer-oil-bdv-test-standards","tag-transformer-oil-breakdown-voltage","tag-transformer-oil-test-kit","tag-transformer-oil-testing-kit"],"yoast_head":"<!-- This site is optimized with the Yoast SEO Premium plugin v22.3 (Yoast SEO v22.3) - https:\/\/yoast.com\/wordpress\/plugins\/seo\/ -->\n<title>Sampling of Transformer Oil - PEQVI Blog<\/title>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/\" \/>\n<meta property=\"og:locale\" content=\"en_US\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Sampling of Transformer Oil\" \/>\n<meta property=\"og:description\" content=\"Preparing of \u2018Electrodes and Test Vessel\u2019 before performing breakdown voltage (BDV) test on insulating oil in service in transformers and switchgear, as defined in IS 6792.\" \/>\n<meta property=\"og:url\" content=\"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/\" \/>\n<meta property=\"og:site_name\" content=\"PEQVI Blog\" \/>\n<meta property=\"article:publisher\" content=\"https:\/\/facebook.com\/PiyushLtd\" \/>\n<meta property=\"article:published_time\" content=\"2021-05-03T12:34:39+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2024-05-21T08:55:56+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/pact.in\/blog\/wp-content\/uploads\/2021\/05\/PACT-Oil-Test-Set-Options.jpg\" \/>\n\t<meta property=\"og:image:width\" content=\"1504\" \/>\n\t<meta property=\"og:image:height\" content=\"516\" \/>\n\t<meta property=\"og:image:type\" content=\"image\/jpeg\" \/>\n<meta name=\"author\" content=\"PGARG\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:creator\" content=\"@PiyushLtd\" \/>\n<meta name=\"twitter:site\" content=\"@PiyushLtd\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"PGARG\" \/>\n\t<meta name=\"twitter:label2\" content=\"Est. reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"2 minutes\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\/\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/#article\",\"isPartOf\":{\"@id\":\"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/\"},\"author\":{\"name\":\"PGARG\",\"@id\":\"https:\/\/pact.in\/blog\/#\/schema\/person\/a8194ee0bb29050c6feecf0651419d74\"},\"headline\":\"Sampling of Transformer Oil\",\"datePublished\":\"2021-05-03T12:34:39+00:00\",\"dateModified\":\"2024-05-21T08:55:56+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/\"},\"wordCount\":313,\"commentCount\":0,\"publisher\":{\"@id\":\"https:\/\/pact.in\/blog\/#organization\"},\"image\":{\"@id\":\"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/#primaryimage\"},\"thumbnailUrl\":\"https:\/\/pact.in\/blog\/wp-content\/uploads\/2021\/05\/PACT-Oil-Test-Set-Options.jpg\",\"keywords\":[\"BDV in transformer\",\"BDV machine\",\"BDV of oil\",\"BDV of transformer oil value\",\"BDV test in transformer\",\"BDV test of oil\",\"BDV test of transformer\",\"BDV tester\",\"BDV testing machine\",\"Breakdown voltage test of transformer oil\",\"Dielectric test of transformer\",\"Dielectric test of transformer oil\",\"Insulation Oil Tester\",\"Oil BDV Test Kit\",\"Oil BDV test of transformer\",\"Oil dielectric test set\",\"Oil Test Set\",\"Transformer oil BDV test kit price\",\"Transformer oil BDV test standards\",\"Transformer oil breakdown voltage\",\"Transformer Oil Test Kit\",\"Transformer oil testing kit\"],\"articleSection\":[\"Oil Test Set\"],\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/#respond\"]}]},{\"@type\":\"WebPage\",\"@id\":\"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/\",\"url\":\"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/\",\"name\":\"Sampling of Transformer Oil - PEQVI Blog\",\"isPartOf\":{\"@id\":\"https:\/\/pact.in\/blog\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/#primaryimage\"},\"image\":{\"@id\":\"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/#primaryimage\"},\"thumbnailUrl\":\"https:\/\/pact.in\/blog\/wp-content\/uploads\/2021\/05\/PACT-Oil-Test-Set-Options.jpg\",\"datePublished\":\"2021-05-03T12:34:39+00:00\",\"dateModified\":\"2024-05-21T08:55:56+00:00\",\"breadcrumb\":{\"@id\":\"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/#breadcrumb\"},\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/#primaryimage\",\"url\":\"https:\/\/pact.in\/blog\/wp-content\/uploads\/2021\/05\/PACT-Oil-Test-Set-Options.jpg\",\"contentUrl\":\"https:\/\/pact.in\/blog\/wp-content\/uploads\/2021\/05\/PACT-Oil-Test-Set-Options.jpg\",\"width\":1504,\"height\":516,\"caption\":\"bdv test of oil\"},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\/\/pact.in\/blog\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Sampling of Transformer Oil\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\/\/pact.in\/blog\/#website\",\"url\":\"https:\/\/pact.in\/blog\/\",\"name\":\"PEQVI Blog\",\"description\":\"Piyush Electronics &amp; Electricals (P) Ltd\",\"publisher\":{\"@id\":\"https:\/\/pact.in\/blog\/#organization\"},\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\/\/pact.in\/blog\/?s={search_term_string}\"},\"query-input\":\"required name=search_term_string\"}],\"inLanguage\":\"en-US\"},{\"@type\":\"Organization\",\"@id\":\"https:\/\/pact.in\/blog\/#organization\",\"name\":\"PEQVI\",\"url\":\"https:\/\/pact.in\/blog\/\",\"logo\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\/\/pact.in\/blog\/#\/schema\/logo\/image\/\",\"url\":\"https:\/\/pact.in\/blog\/wp-content\/uploads\/2024\/04\/peqvi-logo_result.webp\",\"contentUrl\":\"https:\/\/pact.in\/blog\/wp-content\/uploads\/2024\/04\/peqvi-logo_result.webp\",\"width\":990,\"height\":186,\"caption\":\"PEQVI\"},\"image\":{\"@id\":\"https:\/\/pact.in\/blog\/#\/schema\/logo\/image\/\"},\"sameAs\":[\"https:\/\/facebook.com\/PiyushLtd\",\"https:\/\/twitter.com\/PiyushLtd\"]},{\"@type\":\"Person\",\"@id\":\"https:\/\/pact.in\/blog\/#\/schema\/person\/a8194ee0bb29050c6feecf0651419d74\",\"name\":\"PGARG\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\/\/pact.in\/blog\/#\/schema\/person\/image\/\",\"url\":\"https:\/\/secure.gravatar.com\/avatar\/6a0b0ffb9728213f5bb33a0ee32c3828c32612b95baa8851604737fef3f661ff?s=96&d=mm&r=g\",\"contentUrl\":\"https:\/\/secure.gravatar.com\/avatar\/6a0b0ffb9728213f5bb33a0ee32c3828c32612b95baa8851604737fef3f661ff?s=96&d=mm&r=g\",\"caption\":\"PGARG\"},\"url\":\"https:\/\/pact.in\/blog\/author\/jxwl9pib0\/\"}]}<\/script>\n<!-- \/ Yoast SEO Premium plugin. -->","yoast_head_json":{"title":"Sampling of Transformer Oil - PEQVI Blog","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/","og_locale":"en_US","og_type":"article","og_title":"Sampling of Transformer Oil","og_description":"Preparing of \u2018Electrodes and Test Vessel\u2019 before performing breakdown voltage (BDV) test on insulating oil in service in transformers and switchgear, as defined in IS 6792.","og_url":"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/","og_site_name":"PEQVI Blog","article_publisher":"https:\/\/facebook.com\/PiyushLtd","article_published_time":"2021-05-03T12:34:39+00:00","article_modified_time":"2024-05-21T08:55:56+00:00","og_image":[{"width":1504,"height":516,"url":"https:\/\/pact.in\/blog\/wp-content\/uploads\/2021\/05\/PACT-Oil-Test-Set-Options.jpg","type":"image\/jpeg"}],"author":"PGARG","twitter_card":"summary_large_image","twitter_creator":"@PiyushLtd","twitter_site":"@PiyushLtd","twitter_misc":{"Written by":"PGARG","Est. reading time":"2 minutes"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/#article","isPartOf":{"@id":"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/"},"author":{"name":"PGARG","@id":"https:\/\/pact.in\/blog\/#\/schema\/person\/a8194ee0bb29050c6feecf0651419d74"},"headline":"Sampling of Transformer Oil","datePublished":"2021-05-03T12:34:39+00:00","dateModified":"2024-05-21T08:55:56+00:00","mainEntityOfPage":{"@id":"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/"},"wordCount":313,"commentCount":0,"publisher":{"@id":"https:\/\/pact.in\/blog\/#organization"},"image":{"@id":"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/#primaryimage"},"thumbnailUrl":"https:\/\/pact.in\/blog\/wp-content\/uploads\/2021\/05\/PACT-Oil-Test-Set-Options.jpg","keywords":["BDV in transformer","BDV machine","BDV of oil","BDV of transformer oil value","BDV test in transformer","BDV test of oil","BDV test of transformer","BDV tester","BDV testing machine","Breakdown voltage test of transformer oil","Dielectric test of transformer","Dielectric test of transformer oil","Insulation Oil Tester","Oil BDV Test Kit","Oil BDV test of transformer","Oil dielectric test set","Oil Test Set","Transformer oil BDV test kit price","Transformer oil BDV test standards","Transformer oil breakdown voltage","Transformer Oil Test Kit","Transformer oil testing kit"],"articleSection":["Oil Test Set"],"inLanguage":"en-US","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/#respond"]}]},{"@type":"WebPage","@id":"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/","url":"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/","name":"Sampling of Transformer Oil - PEQVI Blog","isPartOf":{"@id":"https:\/\/pact.in\/blog\/#website"},"primaryImageOfPage":{"@id":"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/#primaryimage"},"image":{"@id":"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/#primaryimage"},"thumbnailUrl":"https:\/\/pact.in\/blog\/wp-content\/uploads\/2021\/05\/PACT-Oil-Test-Set-Options.jpg","datePublished":"2021-05-03T12:34:39+00:00","dateModified":"2024-05-21T08:55:56+00:00","breadcrumb":{"@id":"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/#breadcrumb"},"inLanguage":"en-US","potentialAction":[{"@type":"ReadAction","target":["https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/"]}]},{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/#primaryimage","url":"https:\/\/pact.in\/blog\/wp-content\/uploads\/2021\/05\/PACT-Oil-Test-Set-Options.jpg","contentUrl":"https:\/\/pact.in\/blog\/wp-content\/uploads\/2021\/05\/PACT-Oil-Test-Set-Options.jpg","width":1504,"height":516,"caption":"bdv test of oil"},{"@type":"BreadcrumbList","@id":"https:\/\/pact.in\/blog\/2021\/05\/sampling-procedures-for-transformer-oil\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/pact.in\/blog\/"},{"@type":"ListItem","position":2,"name":"Sampling of Transformer Oil"}]},{"@type":"WebSite","@id":"https:\/\/pact.in\/blog\/#website","url":"https:\/\/pact.in\/blog\/","name":"PEQVI Blog","description":"Piyush Electronics &amp; Electricals (P) Ltd","publisher":{"@id":"https:\/\/pact.in\/blog\/#organization"},"potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/pact.in\/blog\/?s={search_term_string}"},"query-input":"required name=search_term_string"}],"inLanguage":"en-US"},{"@type":"Organization","@id":"https:\/\/pact.in\/blog\/#organization","name":"PEQVI","url":"https:\/\/pact.in\/blog\/","logo":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/pact.in\/blog\/#\/schema\/logo\/image\/","url":"https:\/\/pact.in\/blog\/wp-content\/uploads\/2024\/04\/peqvi-logo_result.webp","contentUrl":"https:\/\/pact.in\/blog\/wp-content\/uploads\/2024\/04\/peqvi-logo_result.webp","width":990,"height":186,"caption":"PEQVI"},"image":{"@id":"https:\/\/pact.in\/blog\/#\/schema\/logo\/image\/"},"sameAs":["https:\/\/facebook.com\/PiyushLtd","https:\/\/twitter.com\/PiyushLtd"]},{"@type":"Person","@id":"https:\/\/pact.in\/blog\/#\/schema\/person\/a8194ee0bb29050c6feecf0651419d74","name":"PGARG","image":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/pact.in\/blog\/#\/schema\/person\/image\/","url":"https:\/\/secure.gravatar.com\/avatar\/6a0b0ffb9728213f5bb33a0ee32c3828c32612b95baa8851604737fef3f661ff?s=96&d=mm&r=g","contentUrl":"https:\/\/secure.gravatar.com\/avatar\/6a0b0ffb9728213f5bb33a0ee32c3828c32612b95baa8851604737fef3f661ff?s=96&d=mm&r=g","caption":"PGARG"},"url":"https:\/\/pact.in\/blog\/author\/jxwl9pib0\/"}]}},"_links":{"self":[{"href":"https:\/\/pact.in\/blog\/wp-json\/wp\/v2\/posts\/63","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/pact.in\/blog\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/pact.in\/blog\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/pact.in\/blog\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/pact.in\/blog\/wp-json\/wp\/v2\/comments?post=63"}],"version-history":[{"count":9,"href":"https:\/\/pact.in\/blog\/wp-json\/wp\/v2\/posts\/63\/revisions"}],"predecessor-version":[{"id":104,"href":"https:\/\/pact.in\/blog\/wp-json\/wp\/v2\/posts\/63\/revisions\/104"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/pact.in\/blog\/wp-json\/wp\/v2\/media\/73"}],"wp:attachment":[{"href":"https:\/\/pact.in\/blog\/wp-json\/wp\/v2\/media?parent=63"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/pact.in\/blog\/wp-json\/wp\/v2\/categories?post=63"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/pact.in\/blog\/wp-json\/wp\/v2\/tags?post=63"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}